TS500-Ex-1R-0, 1-Channel Isolating Switching Repeater, Relay Output, 230VAC
- Input for switching contact, proximity switch Namur type acc. to DIN EN 60947-5-6 or opto-coupler
- Input intrinsically safe acc. to ATEX II (1) G [Ex ia] IIC/IIB, ATEX II (1) D [Ex iaD]
- Switchable line fault detection for broken and shorted lines
- Output relay SPDT contact
- Supply voltage 230 VAC
- Power on LED, status / error LED
- 22.5mm case for DIN rail mounting
General information:
Isolating switch-coupler TS500-Ex can be used for monitoring and controlling digital signals out of the hazardous area.
The intrinsically safe input is suitable for switching contact, proximity switch acc. Namur DIN EN 60947-5-6), or passive electronic outputs of other devices.
The devices must be installed out of the Ex-area because only the input is intrinsically safe.
Operating mode:
The Operating mode between input and output can be selected by DIP switches at the front panel (open-circuit or close circuit working).
The frontside LEDs indicate the activated output.
Line fault detection:
When operating with Namur proximity switches the controlling function for broken line and shorted line can be activated by DIP switch.
In case of an error, the output changes to inactive and the LED indicators are flashing.
For connection with switching contacts external resistors are necessary.
Technical data:
Explosion protection:
Certification: DMT 99 ATEX E 079
Approval: EX II (1) GD [Ex ia] IIC/IIB or II (1) D [Ex iaD]
Max. voltage (no load) U0: 10.6 V
Max. short cirduit current I0: 26.8 mA
Max. power consumption P0: 71.0 mW
Input classification EEx ia/IIB ia/IIC
Max. external capacity: 16.2 µF 2.3 µF
Max. external inductivity: 110.0 mH 20.0 mH
Internal capacity: negligible
Internal inductivity: 36 µH
Power supply:
Supply voltage: 230VAC ±10 % , 47 ... 63 Hz
Power consumption: < 2 W
Operating temperature: -10 ... 55 °C (14 ... 131 °F)
Rated voltage : 400V AC acc. VDE0110 group 2 between input/output/supply voltage
Test voltage: 4kV DC between input/output/supply voltage
CE-conformity: ATEX directive 94/9/EG
EN 60079-0:2006 EN 60079-11:2007
EN 61241-0:2006 EN 61241-11:2007
IEC 61000-4-2/3/4/5/6/8/11
Input (intrinsically safe):
No load voltage: approx. 8 V (acc. to DIN EN 60947-5-6, Namur)
Short circuit current: approx. 8 mA (acc. to DIN EN 60947-5-6, Namur)
Switching point: inactive <=1,2 mA, active >=2,1 mA, hysteresis ca. 0,5 mA
Broken line detection: <=0.1mA
Shorted line detection: >=7.5mA
Output (relay):
Switching capacity: <253 VAC <100 VA <2 A; <100 VDC <50 W <2 A
Max. switching frequency: 5 Hz
Max. switching delay: 20 ms
Case: standard case of polycarbonate 8020 UL94V-1 acc. to DIN EN 60715:2001-09
Weight: approx. 200 g
Protection: case IP30, terminals IP20 finger safe acc. to German BGV
Option (upon request and surcharge):
1- channel transistor output instead of the relay output