Universal Isolating Amplifier, TV125L

Item number: TV125L

  • safe galvanic isolation between input/output/auxiliary voltage
  • step response T90: 40ms
  • output deviation <0.2% of the limit value
  • overload protection of the current input with automatically resetting fuse
  • operating display and status messages via two-colour LED
  • configuration via front DIP switches
  • plug-in terminal strips
  • slim installation width of 12.5mm for carrier rail mounting TS 35
  • Category: Measuring Transducers


    110,67 €

    including 19% VAT.

    Exp. shipping time: ca. 1-2 weeks

    : 5 workdays

    pc.


    Description

    Universal Isolating Amplifier, TV125L

    • safe galvanic isolation between input/output/auxiliary voltage
    • step response T90: 40ms
    • output deviation <0.2% of the limit value
    • overload protection of the current input with automatically resetting fuse
    • operating display and status messages via two-colour LED
    • configuration via front DIP switches
    • plug-in terminal strips
    • slim installation width of 12.5mm for carrier rail mounting TS 35

    This isolating amplifier is suitable for potential isolation or for conversion of industry standard signals. The universal layout of the inputs and the output enables a broad range of applications with only one type of device. The plug-in terminal strips enable simple and time-saving wiring. The configuration is also quick and easy with the front DIP switches.

    The input measuring ranges can be switched between 0...20mA and 4...20mA or 0...10V and 2...10V with a DIP switch on the front.
    With the microprocessor-controlled measurement logging, undercutting and exceeding of the measurement range are detected and indicated via a two-colour status LED on the front side. Furthermore the current output is set to a defined starting or final value.

    The current input is protected with an automatically resetting fuse (PTC) against static overvoltages up to 32VAC/DC.
    The required auxiliary energy is less than 0.5VA.
    The three circuits: Inputs, outputs and auxiliary voltage are galvanically separated with strengthened isolation.

    Technical data:

    Hilfsenergie
    Auxilary power: 15...30VDC
    Power consumption: <0.5VA
    Conformity: CE, directive 2004/108/EG
    EMV: DIN EN 61326-1: 2013-07, Klasse A
    Standards: DIN EN 61010-1: 2011-07
                  DIN EN 61010-2: 2011-07
    Rated voltage: 300VAC/DC in accordance with DIN EN 61010-1
                           with overvoltage category 2 and degree of contamination between all circuits 
                           safe separation with strengthened isolation
    Test voltage: 3kVAC, 50Hz, 1min
                          input/output/auxiliary voltage

    Environmental conditions
    Operationg temperature: -10...+60°C
    Storage temperature: -20...+60°C
    Air humidity: <95% RH, non condensating

    Inputs
    Voltage input: 0...10V or 2...10V selectable
                          Ri = 47kOhm. overload max. 32VAC/DC
    Current input: 0...20mA or 4...20mA selectable
                          Ri = 48 Ohm +15 Ohm (RiPTC)
                          overload max. 32VAC/DC in accordance with DIN EN 61010-2-30

    Output
    Current output: 0...20mA or 4...20mA selectable. Burden <150 Ohm
    Step response: 40ms
    Standard error: <0.2% of final value
    Temperature coefficient: <0.01% / K

    Housing
    Material: Polyamide (PA) 6.6, UL94V-0
    Weight: 91g
    Colour: light grey
    Installation width: 12.5mm
    Dimensions (HxD): 108mm x 114mm
    Mounting: Carrier rail mounting TS35 DIN EN 60715