Description
CVT500, Current and Voltage Transmitter
- Measuring input for DC and sinusoidal AC signals
- Arithmetic average value measurement RMS calibrated
- Frequenca range 40...200Hz
Transmitters CVT500 convert current or voltage signals into proportional industry standard signals. Currents up to 5AAC/DC and voltages up to 400VAC/DC can be fed directly into the transmitter. For higher AC currents a current transformer respective for higher AC voltages a voltage transformer has to be fitted.
The transmitters are available in two versions regarding the supply voltage.
Please select the requested supply voltage when ordering.
Technical data:
Auxiliary energy
Supply voltage: 230VAC ±10% or 24VDC ±15%
Frequency: AC: 47...63Hz
Power consumption: <3VA
Operating temperature: -10...+50°C
CE conformity: EN 55022, EN 60555, IEC 61000-4-3/4/5/11/13
Inputs
Basic accuracy: <= 0.5% (<= 0.2% with single adjustment)
Frequency AC: 40...200Hz (other ranges on request)
Standard measuring ranges
Current: 0...1A and 0...5A sinusoidal or DC
Ri: 20mOhm (5A input) or 100mOhm (1A input)
Overload: 2-times, 4-times for max. 5s
Voltage: 0...125V and 0...250VAC or DC
Ri: 600kOhm (125V input) or 1.2MOhm (250V input)
Überlast: max. 500VAC/DC
Output
Output changing
Voltage/current: link between terminal 8 and 9
Current output: 0/4...20mA selectable, burden <=500 Ohm
Rise time (T90): <650ms
Burden error: <0.1% (RL = <200 Ohm), <0.ö2% (RL = <500 Ohm)
Voltage: 0/2...10V selectable, load max. 10mA
Housing
Type: Standard case of Polycarbonate 8020 UL94V-1
Weight: ca. 200g
Connection: Screw terminals with pressure plate, max. 2.5mm wire
Protection: Case: IP30, terminals: IP20, finger safe acc. to German BGV A3