STL50Ex-5-1R-0, Safety Temperature Limiter for Thermocouples, 230VAC

Item number: STL50Ex-5-1R-0

  • Input double thermocouples, intrinsically safe ATEX II (1) G [EX ia] IIC/IIB or II (1) D [Ex iaD]
  • For certified thermocouples of types J, K, N and S
  • Useful as temperature limiter/guard and exhaust gas temperature limiter
  • Certified according to EN 14597 SIL 2
  • Auxiliary voltage: 230VAC
  • Alarm output: 1 relay; SPDT
  • Programming via backlit LCD graphic display
  • Category: Limit Monitors


    873,46 €

    including 19% VAT.

    Exp. shipping time: ca. 1-2 weeks

    : 5 workdays



    Description

    STL50Ex-5-1R-0, Safety Temperature Limiter for Thermocouples,  230VAC

    • Useful as temperature limiter/guard and exhaust gas temperature limiter
    • Certified according to EN 14597  SIL 2
    • Input double thermocouple,  intrinsically safe ATEX II (1) G [EX ia] IIC/IIB or II (1) D [Ex iaD]
    • Alarm output: 1 relay; SPDT
    • Programming via backlit LCD graphic display
    Characteristics:
    The STL50Ex safety temperature limiter is used where ever thermal processes in explosion-prone environments (up to zone 0) must be monitored and the system must be transferred into a safe operational state in case of fault. If the permissible temperature limit value is reached, or if a fault occurs within the permissible temperature range on the monitoring equipment (sensor open, sensor short-circuit, failure of a component part in the device, fault in the software, failure or inadmissible value of the supply voltage etc.), the STL50Ex switches off without delay.
    The alarm contact is activated, the LED ALARM on the front panel and the back-lighting of the display light up, and the error cause is indicated as plain text on the display.
    In addition, there is a 24 V DC signal present on the terminals 17-18 for an external alarm signal.

    Brief description:
    Programming:
    The device is programmed using the front side buttons, in connection with the graphics display.

    Operating modes:
    The device can be used as:
       STB:    Maximum or minimum monitoring with lock. Reset following removal of the fault through actuation of the front-sided button or externally connected pushbutton
    ASTB:    As before, however for the monitoring of the exhaust gas temperature
     STW:    Maximum or minimum monitoring without lock. Reset automatically on return into the permissible range

    Switching hysteresis always acts in the direction of safe range.

    Error log memory:
    The last fault is stored as plain text and can be called up in the working level and deleted.
     
    Temperature probe:
    Attention: The device may be operated only with temperature probes which are certified according to DIN EN 14597!

    Technical data:
    Input double thermocouple: intrinsically safe ATEX II (1) G [EX ia] IIC/IIB or II (1) D [Ex iaD]       
    Certification: TUV 07 ATEX 554295
    Input thermocouples: 
                   J (Fe-CuNi): -100.0 to +800.0 °C
                   K (NiCr-Ni): -150 to +1200 °C
                   N (NiCrSi-NiSi): -150 to +1200 °C
                   S (Pt10Rh-Pt): 0 to +1600 °C
    Output: relay, 1 x CO contacts (SPDT)
    Power supply: 230VAC ± 10%
                          (115VAC version available upon request)
    Housing material: polyamide (PA) 6.6 UL94 V-0
    Housing: DIN rail mounting TS35
    Floor space: 50x100 mm² (BxH) 
    Mounting height: 110 mm
    Weight: ca. 450g
    Connection: screw terminals 0.14 to 2.5mm²
    Housing protection: IP20, DIN EN 60529, BGV A3


    Please note: Sensors need to be ordered separately!

    Ratings (0)

    Average product review

    Write your first review and help others with their purchase decision: