Limit Value Switch GS125M with Universal Input and Wide-Range Mains Adaptor

Item number: GS125M

  • universal input for industry standard signals, Pt100, thermocouple and potentiometer
  • 1 relay output
  • adjustable min/max contact function 
  • 2-colour illuminated  scales for limit value adjustment
  • monitoring of sensor break and short-circuit with Pt100 sensors
  • wide-range mains adaptor
  • functional safety up to SIL2
  • housing width only 12.5mm
  • removable coded terminals
  • carrier rail mounting TS35 EN60715
  • safe galvanic isolation between input/output and auxiliary voltage
  • Category: Limit Monitors


    171,36 €

    including 19% VAT.

    Exp. shipping time: ca. 1-2 weeks

    : 5 workdays

    pc.


    Description

    Limit Value Switch GS125M with Universal Input and Wide-Range Mains Adaptor

    • universal input for industry standard signals, Pt100, thermocouple and potentiometer
    • 1 relay output
    • adjustable min/max contact function 
    • 2-colour illuminated  scales for limit value adjustment
    • monitoring of sensor break and short-circuit with Pt100 sensors
    • wide-range mains adaptor
    • functional safety up to SIL2
    • housing width only 12.5mm
    • removable coded terminals
    • carrier rail mounting TS35 EN60715
    • safe galvanic isolation between input/output and auxiliary voltage

    This limit value switch is used in switch cabinets for process monitoring or for simple process regulation.
    Both temperatures and derived variables such as voltage, current and resistance are used as control signals. In the process, 1 or 2 limit values can be monitored.

    The universal configurability of the measuring inputs reduces the stock requirement for various applications.

    The housing widh of only 12.5mm enables space-saving installation in the switch cabinet. The scales for the limit value setting, illuminated red or green depending on the switch status, also enable operatingin dark environments. 

    For the assignment of the measuring unit to the scale labelling, 24 transparent adhesive labels are supplied. They can be fixed between the adjusting wheels on the front panel. 

    Measurement inputs, selectable via DIP switch:
    Industry standard signals: 0/2...10V
                                           0/4...20mA
    Potentiometer: 500 Ohm ... 20kOhm
    Pt100:  0...50°C
                0...100°C
                0...150°C
                0...200°C
                0...300°C
                0...500°C

    Thermocouple
    FeCuNI, type J: 0...250°C
                             0...500°C
    NiCrNi, type K: 0...500°C
                             0...750°C
                             0...1000°C
    PtRhPt, type S: 0...1500°C


    Technical data:
    supply voltage: (wide-range power supply): 20...125VDC and
                                                                     20...250VAC (47...63Hz), max. 1,5W
    rated voltage: 253VAC
    test voltage: 3kVAC between input/relay output and auxiliary voltage
    operating temperature: -10...+60°C
    storage temperature: -20...+80°C
    air humidity: 10...90% (non-condensing)

    Measurement inputs
    voltage: 0/2...10V, Ri ca. 20kOhm
    current: 0/4...20mA, Ri ca. 60 Ohm
    Pt100: linearised, measurement current approx. 1.6mA
               relays become inactive if there is a sensor break or short-circuit
    thermocouple: linearised with cold junction compensation
    resistance: (3-wire), nominal value 500 Ohm ... 20kOhm
                       internal reference voltage ca. 1.5V

    Relay output, 1 changeover contact
    switching voltage: <250VAC, <2A, < 500VA
                                <125VDC, <0,2A, <25W
                                <30VDC, <2A, <60W
    switching frequency: max. 5Hz
    switching hysteresis: ca. 1%

    Functional safety: SIL2 in accordance to EN61508

    Setpoint setting: scale precision: 2%

    Actual value output (option): 4...20mA, burden max. 120 Ohm, no galvanic isolation from the input signal


    Options against extra charge:
  • actual value output
  • push-in terminals
  • supply voltage 24VDC with carrier rail bus connection
  • 2 output relays (universal connection)
  • 2 output relays (potential-free N.O. contacts)