TS500-Ex-2R-5, 2-Channel Isolating Switching Repeater, 2 Relay Outputs, 24VDC

Item number: TS500-Ex-2R-5

  • Inputs for switching contact, proximity switch Namur type acc. to DIN EN 60947-5-6 or opto-coupler
  • Inputs intrinsically safe acc. to ATEX II (1) G [Ex ia] IIC/IIB, ATEX II (1) D [Ex iaD]
  • Switchable line fault detection for broken and shorted lines
  • Output relays SPDT contact>
  • Supply voltage 24VDC
  • Power on LED, status / error LED
  • 22.5mm case for DIN rail mounting
  • Category: Measuring Transducers


    167,79 €

    including19% VAT.

    Exp. shipping time: ca. 1 week

    : 5 workdays

    pc.


    Description

    TS500-Ex-2R-5, 2-Channel Isolating Switching Repeater, 2 Relay Outputs, 24VDC

    • Inputs for switching contact, proximity switch Namur type acc. to DIN EN 60947-5-6 or opto-coupler
    • Inputs intrinsically safe acc. to ATEX II (1) G [Ex ia] IIC/IIB, ATEX II (1) D [Ex iaD]
    • Switchable line fault detection for broken and shorted lines
    • Output relays SPDT contact>
    • Supply voltage 24VDC
    • Power on LED, status / error LED
    • 22.5mm case for DIN rail mounting


    General information:
    Isolating switch-coupler TS500-Ex can be used for monitoring and controlling digital signals out of the hazardous area.
    The intrinsically safe input is suitable for switching contact, proximity switch acc. Namur DIN EN 60947-5-6), or passive electronic outputs of other devices.
    The devices must be installed out of the Ex-area because only the input is intrinsically safe.

    Operating mode:
    The Operating mode between input and output can be selected by DIP switches at the front panel (open-circuit or close circuit working).
    The frontside LEDs indicate the activated output.

    Line fault detection:
    When operating with Namur proximity switches the controlling function for broken line and shorted line can be activated by DIP switch.
    In case of an error, the output changes to inactive and the LED indicators are flashing.
    For connection with switching contacts external resistors are necessary.


    Technical data:

    Explosion protection:
    Certification: DMT 99 ATEX E 079
    Approval: EX II (1) GD [Ex ia] IIC/IIB or II (1) D [Ex iaD]
    Max. voltage (no load) U0: 10.6 V
    Max. short circuit current I0: 26.8 mA
    Max. power consumption P0: 71.0 mW

    Input classification EExia/IIBia/IIC
    Max. external capacity: 16.2 F 2.3 F
    Max. external inductivity: 110.0 mH20.0 mH
    Internal capacity: negligible
    Internal inductivity: 36 H

    Power supply:
    Supply voltage: 24VDC 15% (safety voltage 253VAC/125VDC)
    Power consumption: < 2 W
    Operating temperature: -10 ... 55 C (14 ... 131 F)
    Rated voltage : 400V AC acc. VDE0110 group 2 between input/output/supply voltage
    Test voltage: 4kV DC between input/output/supply voltage
    CE-conformity: ATEX directive 94/9/EG
    EN 60079-0:2006 EN 60079-11:2007
    EN 61241-0:2006 EN 61241-11:2007
    IEC 61000-4-2/3/4/5/6/8/11

    Inputs (intrinsically safe):
    No load voltage: approx. 8 V (acc. to DIN EN 60947-5-6, Namur)
    Short circuit current: approx. 8 mA (acc. to DIN EN 60947-5-6, Namur)
    Switching point: inactive <=1,2 mA, active >=2,1 mA, hysteresis ca. 0,5 mA
    Broken line detection: <=0.1mA
    Shorted line detection: >=7.5mA

    Outputs (relay):
    Switching capacity: <253 VAC <100 VA <2 A; <100 VDC <50 W <2 A
    Max. switching frequency: 5 Hz
    Max. switching delay: 50 ms

    Case: standard case of polycarbonate 8020 UL94V-1 acc. to DIN EN 60715:2001-09
    Weight: approx. 200 g
    Protection: case IP30, terminals IP20 finger safe acc. to German BGV


    Option (upon request and surcharge):
    2- channel transistor outputs instead of the relay outputs





    Ratings (0)

    Average product review

    Write your first review and help others with their purchase decision: