Description
Limit Monitor GS500 for Industry Standard Signals
The GS500 can be used for monitoring physical processes presented as industry standard signal. Limit value can be set from 0..100%. The adjustable switching delay prevents that short signal peaks does not activate the alarm.
By an adjustable switching hysteresis a frequently switching can be suppressed with small signal variations.
Technical data:
Power supply:
Auxiliary voltage: 230VAC 10% or 24VDC -30/+40% (please select when ordering)
Frequency: AC: 47...36Hz
Power consumption: <3VA
Operating temperature: -10...+50°C
CE conformity: EN 55022, IEC 61000-4-3/4/5/11/13, EN 60555
Inputs:
Scale error: <= 2%
Repeatability: <= 0,1%
Current:
Measuring range: 0/4...20mA selectable
Input resistance: 125Ohm
Overload: 2-times, 4-times für max. 5s
Voltage:
Measuring range: 0/2...10VDC selectable
Input resistance: 40kOhm
Overload: max. 100VDC
Outputs:
Relay SPDT: 250VAC < 250VA < 2A; 100VDC <50W <1A
Switching function: min./max. selectable
Hysteresis: 1...25%
Time delay: 0.1...8s
Case:
Model: standard case polycarbonate 8020 UL 94 V-1 to DIN EN 60715:2001-09
Weight: ca. 200g
Protection class: Case IP30, terminals IP20, (BGV A3)
Connection: screw terminals, max. 2,5mm²