Current and Voltage Monitoring Relay, CVG500

Item number: CVG500ff

  • arithmetic average value measuring RMS calibrated
  • contact function min/max selectable
  • hysteresis and tyme delay adjustable
  • Category: Limit Monitors

    Supply Voltage

    178,50 €

    including 19% VAT.

    Exp. shipping time: ca. 1-2 weeks

    There are variations of this item. Please select the variation you wish.


    Description

    Current and Voltage Monitoring Relay, CVG500

    • arithmetic average value measuring RMS calibrated
    • contact function min/max selectable
    • hysteresis and tyme delay adjustable

    This monitoring relay can be used for monitoring current or voltage levels. It is designed for input 0...1/5AAC/DC and 0...125/250VAC/DC.
    There are two versions available regarding the supply voltage. Please select the requested supply voltage when ordering.

    Technical data:

    Auxiliary energy
    Supply voltage:  230VAC ±10% or 24VDC ±15%
    Frequency: AC: 47...63Hz
    Power consumption: <3VA
    Operating temperature: -10...+50°C (-25...+70°C on request)
    CE conformity: EN 55022, EN 60555, IEC 61000-4-3/4/5/11/13

    Inputs
    Scale error: <=2%
    Frequency AC: 40...200Hz (other ranges on request)

    Standard measuring ranges
    Current: 0...1AACand 0...5AAC (sinusoidal) or DC
         Ri: 20mOhm (5A input) or 100mOhm (1A input)
         Overload: 2-times, 4-times for max. 5s
    Voltage: 0...125VAC and 0...250VAC (sinusoidal) or DC
         Ri: 600kOhm (125V input) or 1.2MOhm (250V input)
         Overload: max. 500VAC/DC

    Output
    Changeover relay: 250VAC: <250VA, <2A; 200VDC: <50W, <1A
    Switching function: min./max. selectable
    Hysteresis: 1...25%
    Time delay: 0.1...8sec.