AC Current Transmitter CT500P

Item number: CT500Pff

  • 1-or 2-channel device
  • measuring ranges 0...1AAC or 0...5AAC
  • arithmetic average value measurement RMS calibrated
  • frequency range 45...400Hz
  • loop voltage 14...30VDC
  • Category: Measuring Transducers

    Channels/Current Range

    starting from 138,04 €

    including 19% VAT.

    Exp. shipping time: ca. 1-2 weeks

    There are variations of this item. Please select the variation you wish.


    Description

    AC Current Transmitter CT500P

    • 1-or 2-channel device
    • measuring ranges 0...1AAC or 0...5AAC
    • arithmetic average value measurement RMS calibrated
    • frequency range 45...400Hz
    • loop voltage 14...30VDC
    This transmitter converts AC current from 0...1AAC or 0...5AAC into the proportional standard signal 4...20mA.
    The CT500P operates like a 2-wire transmitter which is supplied from the measuring device (e.g. active PLC input circuit board).
    The device is available in four versions which are different in the number of channels and the current range. Please select the required version when ordering.

    Technical data:
     
    Supply voltage
    Loop voltage: 14...30VDC
    Operating temperature: -10...+60°C
    CE conformity : EN55022, EN60555, IEC61000-4-4/5

    Input: 1 or 2 channels
    AC current: 0...1AAC or 0...5AAC, overload max. 10A
    Ri: <20mOhm
    Frequency: 45...400Hz fundamental wave, 16 2/3 Hz on request
    End value: adjustable ±5%

    Output
    Current: 4...20mA, burden Rmax. = (UB-14V) : 20mA
    Rise time (T90): < = 1s
    Basic accuracy: < = 0,2%

    Case
    Design: Polycarbonate, UL94 V-0, TS35 according to DIN EN 60715:2001-09
    Weight: ca. 200g
    Connection: screw terminals, max. 2,5mm²
    Protection class: case IP30, terminals IP20 according to BGV A3