Peak Tech 2685Peak Tech 2700, Earth Resistance Tester $ask_seller
|
Peak Tech 2695, Insulation Tester
|
|
|
Peak Tech 2695, Digital Insulation Tester 3 ½-digit |
|
|
|
|
( 10. PeakTech )
|
€ 174,93 (including 19 % tax)
|
|
Peak Tech 2695, Digital Insulation Tester 3 ½-digit Very electrical apparatus and installation need to be safe for the user and for the equipment itself. Electrical conductors of electricity need to be insulated from each other, so that they do not create electrical hazard or unnecessary consumption. Badly insulated circuits can create leakage current which can be dangerous and trip your GFCI, RCCB or ELCB. Each country regulate those levels at which the insulation is acceptable. Check the continuity of wires, complete circuits connections, closure of contacts, circuit breakers, fuses, bounding resistance of connections, etc. are all very important.

|
large dual LC-display with analogue bargraph and backlight
|

|
MIN/MAX recording and DATA-Hold
|

|
auto-discharge of capacitive voltage for added user protection
|

|
live circuit detection prevents insulation test if voltage >30 V is detected
|

|
low battery indication
|

|
auto power off
|

|
safety: EN-61010-1; CAT III 1000 V
|

|
accessories: case, batteries, test leads and manual
|
Technical data:
insulation resistance
|
4/40/400/4000 MΩ - 1 kΩ; ± 2 % + 10 dgt.
|
test voltage
|
125/250/500/1000 V; +10% / -0 %
|
short circuit current
|
< 1 mA
|
test curent
|
1 mA with 125 kW load at 125 V 1 mA with 250 kW load at 250 V 1 mA with 500 kW load at 500 V 1 mA with 1 MW load at 1000 V
|
AC voltage
|
750 V - 1 V; ± 1,2 % + 10 dgt.
|
DC voltage
|
1000 V - 1 V; ± 0,8 % + 3 dgt.
|
resistance
|
40/400 Ω - 10 mΩ; ± 1,2 % + 3 dgt.
|
operation voltage
|
6 x 1,5 V AA (UM-3) batteries
|
dimensions (WxHxD)
|
92 x 200 x 50 mm
|
weight
|
700 g |
|
|
|
|
|
|
|
|
|
|
|
|
Copyright © 2013 PSE- Priggen Special Electronic, Online Shop, Messgeräte, Measuring Instruments. All rights reserved.
|
|