STL50-1-1R-5, Safety Temperature LimiterSTL50-5-1R-5, Safety Temperature Limiter

STL50-5-1R-0, Safety Temperature Limiter

 ( 16. Martens )
STL50-5-1R-0, Safety Temperature Limiter
View Full-Size Image


€ 542,64 (including 19 % tax)


STL50-5-1R-0, Safety Temperature Limiter for Thermocouples, Supply Voltage: 230VAC
 
For thermocouples of the types J, K, N and S, certified to DIN EN 14597 (replaces DIN 3440), SIL 2.
 
Features
  •     For use as:
          STB     Protection -  temperature limiter
          ASTB   Exhaust gas protection -  temperature limiter
          STW    Protection -  temperature monitor
  •     Certified according to EN 61508 SIL2
  •     Input: double thermocouple J, K, N and S
  •     Temperature limit value and switching hysteresis programmable
  •     Basic accuracy: < 0.5% ± 2 digits
  •     Reaction time: ≤ 0.5 sec
  •     Alarm output: 1 relay, CO; SPDT
  •     Clear text programming via graphic display 128x64 pixel,
        with white background lighting
  •     Memory function for error report
  •     Operation-lock feature (password protection)
  •     Case for switchboard installation
 
General:
The STL50 safety temperature limiter is used where ever thermal processes must be monitored and the system must be transferred into a safe operational state in case of fault. If the permissible temperature limit value is reached, or if a fault occurs within the permissible temperature range on the monitoring equipment (sensor open, sensor short-circuit, failure of a component part in the device, fault in the software, failure or inadmissible value of the Supply voltage etc.), the STL50 switches off without delay.
The alarm contact is activated, the LED ALARM on the front panel and the back-lighting of the display light up, and the error cause is indicated as plain text on the display.
In addition, there is a 24 V DC signal present on the terminals 17-18 for an external alarm signal.
 

Brief description:
Programming:  The device is programmed using the front side buttons, in connection with the graphics display.
Operating modes:  The device can be used as:
          STB ->    Maximum or minimum monitoring with lock
                          Reset following removal of the fault through actuation of the front-sided button
                          or externally connected pushbutton
          ASTB -> As before, however for the monitoring of the exhaust gas temperature
          STW  ->  Maximum or minimum monitoring without lock
                          Reset automatically on return into the permissible range
Switching hysteresis: Always acts in the direction of safe range.
Error log memory: The last fault is stored as plain text and can be called up in the working level and deleted.
 
Temperature probe: Attention: The device may be operated only with temperature probes which are certified according to DIN EN 14597

Technical data:
Housing: DIN rail mounting TS35
                  Floor space: 50x100 mm² (BxH)
                  Mounting height: 110 mm
Input thermocouples: 
               J (Fe-CuNi): -100.0 to +800.0 °C
               K (NiCr-Ni): -150 to +1200 °C
               N (NiCrSi-NiSi): -150 to +1200 °C
               S (Pt10Rh-Pt): 0 to +1600 °C
Output: relay, 1 x CO contacts
Supply voltage: 230 VAC ± 10 %, 50-60 Hz

Please note: Sensors need to be ordered separately!